CA07074E_Above Ground Enclosures
Cable Accessories
15 kv Load Break Junctions
215J2U
|
215J3U
|
215J4U
RATINGS
Max. continuous voltage
: 8.3 kV phase-to-ground 14.4 kV phase-to-phase
Continuous current
: 200 A rms
SHORT-TIME CURRENT RATINGS
0.17 seconds duration 3.00 seconds duration
: 10,000 A rms symmetrical
: 3,500 A rms symmetrical
INSULATION WITHSTAND VOLTAGES
Basic Impulse Level (1.2 x 50 µ sec.\wave) 60 Hertz (one minute) Corona Extinction Voltage (5 pC)
: 95 kV crest
: 34 kV rms
: 11 kV rms
SWITCHING
1-phase and 3-phase circuits 8.3 kV phase-to-ground, 14.4 kV maximum across the open contacts.
: 10 loadmake/loadbreak operations at 200 A with 70-80% lagging power factor.
FAULT CLOSURE One fault-close operation at 8.3 kV phase-to-ground, or 14.4 kV phase-to-phase; 10,000 A rms symmetrical, 10 cycles, (0. 17 seconds).
Features • Red snuffer nose for 15kV Class product recognition. • Yellow seating indicator ring molded in for positive indication that mating product is fully seated.
PRODUCTION TESTS
100% factory test for partial discharge and either AC HI-POT (34 kV for 60 seconds) or impulse (BIL) (95 kV 1.2 x 50 µ sec.\wave).
25/28 kv Load Break Junctions
228J2U
|
228J3U
|
228J4U
RATINGS
Max. continuous voltage
: 16.2 kV phase-to-ground 28.0 kV phase-to-phase
Continuous current
: 200 A rms
SHORT-TIME CURRENT RATINGS
0.17 seconds duration 3.00 seconds duration
: 10,000 A rms symmetrical
: 3,500 A rms symmetrical
INSULATION WITHSTAND VOLTAGES
Basic Impulse Level (1.2 x 50 µ sec.\wave) 60 Hertz (one minute) Corona Extinction Voltage (5 pC)
: 125 kV crest
: 45 kV rms
: 21.5 kV rms
SWITCHING
1-phase and 3-phase circuits 16.2 kV phase-to-ground, 28.0 kV maximum across the open contacts.
: 10 loadmake/loadbreak operations at 200 A with 70-80% lagging power factor.
Features • Blue snuffer nose for 25/28kV Class product recognition. • Yellow seating indicator ring molded in for positive indication that mating product is fully seated. • Vented seating indicator to reduce partial vacuum flashovers.
FAULT CLOSURE One fault-close operation at 16.2 kV phase-to-ground, or 28.0 kV phase-to-phase; 10,000 A rms symmetrical, 10 cycles, (0. 17 seconds).
PRODUCTION TESTS
100% factory test for partial discharge and either AC HI-POT (45 kV for 60 seconds) or impulse (BIL) (125 kV 1.2 x 50 µ sec. wave).