CA07074E_Above Ground Enclosures

Cable Accessories

15 kv Load Break Junctions

215J2U

|

215J3U

|

215J4U

RATINGS

Max. continuous voltage

: 8.3 kV phase-to-ground 14.4 kV phase-to-phase

Continuous current

: 200 A rms

SHORT-TIME CURRENT RATINGS

0.17 seconds duration 3.00 seconds duration

: 10,000 A rms symmetrical

: 3,500 A rms symmetrical

INSULATION WITHSTAND VOLTAGES

Basic Impulse Level (1.2 x 50 µ sec.\wave) 60 Hertz (one minute) Corona Extinction Voltage (5 pC)

: 95 kV crest

: 34 kV rms

: 11 kV rms

SWITCHING

1-phase and 3-phase circuits 8.3 kV phase-to-ground, 14.4 kV maximum across the open contacts.

: 10 loadmake/loadbreak operations at 200 A with 70-80% lagging power factor.

FAULT CLOSURE One fault-close operation at 8.3 kV phase-to-ground, or 14.4 kV phase-to-phase; 10,000 A rms symmetrical, 10 cycles, (0. 17 seconds).

Features • Red snuffer nose for 15kV Class product recognition. • Yellow seating indicator ring molded in for positive indication that mating product is fully seated.

PRODUCTION TESTS

100% factory test for partial discharge and either AC HI-POT (34 kV for 60 seconds) or impulse (BIL) (95 kV 1.2 x 50 µ sec.\wave).

25/28 kv Load Break Junctions

228J2U

|

228J3U

|

228J4U

RATINGS

Max. continuous voltage

: 16.2 kV phase-to-ground 28.0 kV phase-to-phase

Continuous current

: 200 A rms

SHORT-TIME CURRENT RATINGS

0.17 seconds duration 3.00 seconds duration

: 10,000 A rms symmetrical

: 3,500 A rms symmetrical

INSULATION WITHSTAND VOLTAGES

Basic Impulse Level (1.2 x 50 µ sec.\wave) 60 Hertz (one minute) Corona Extinction Voltage (5 pC)

: 125 kV crest

: 45 kV rms

: 21.5 kV rms

SWITCHING

1-phase and 3-phase circuits 16.2 kV phase-to-ground, 28.0 kV maximum across the open contacts.

: 10 loadmake/loadbreak operations at 200 A with 70-80% lagging power factor.

Features • Blue snuffer nose for 25/28kV Class product recognition. • Yellow seating indicator ring molded in for positive indication that mating product is fully seated. • Vented seating indicator to reduce partial vacuum flashovers.

FAULT CLOSURE One fault-close operation at 16.2 kV phase-to-ground, or 28.0 kV phase-to-phase; 10,000 A rms symmetrical, 10 cycles, (0. 17 seconds).

PRODUCTION TESTS

100% factory test for partial discharge and either AC HI-POT (45 kV for 60 seconds) or impulse (BIL) (125 kV 1.2 x 50 µ sec. wave).

52 | hubbellpowersystems.com | 800.346.3062

Made with FlippingBook flipbook maker