Compression Grounding
HYGROUND ® Compression System HYTAP™ Type YGHHC-C Double Figure C Connector
HYTAP™ Type YGHHC-C Double Figure C Connector
IEEE-837 2014 Qualified!
Irreversible compression ground tap figure “C” connectors. Accommodates all cable combinations from #6 solid through 500 kcmil. “C”- shaped opening permits placing two continuous parallel cables into conductor groove. The YGHHC-C series is qualified to IEEE-837 2014. Prefilled with PENETROX™compound and strip sealed.
Commercial Copper Cable toCable or Cable toGroundRod
InstallationData
StrandedCopper CableRangeMetric
Die Index No.
No. of Crimps
Catalog Number
H L Z
750, 35 Series
45 Series
46 Series
Run
Tap
Run
Tap
35mm² (7.62mm) 70mm² (10.9mm) 95mm² (12.5mm) 120mm² (14.4mm) 95mm² (12.5mm) 120mm² (14.4mm) 150mm² (16mm) 240mm² (20.35mm) 150mm² (16mm) 240mm² (20.35mm) 150mm² (16mm) 240mm² (20.35mm)
35mm² (7.62mm) 70mm² (10.9mm) 10mm² (4.10mm) 70mm² (10.90mm) 95mm² (12.5mm) 120mm² (14.4mm) 10mm² (4.10mm) 70mm² (10.90mm) 95mm² (12.5mm) 120mm² (14.4mm) 150mm² (16mm) 240mm² (20.35mm)
1 Str. (0.328) 2/0 Str. (0.419) 3/8" Rod
1 Str. (0.328) 2/0 Str. (0.419)
1.54 [39]
0.75 [19]
1.88 [48]
YGHHC26C26
O UO
UO UO 2
3/0 Str. (0.470) 250 kcmil (0.575) 1/2" or 5/8" Rod 3/0 Str. (0.470) 250 kcmil (0.575) 1/2" or 5/8" Rod 300 kcmil (0.630) 500 kcmil (0.813) 3/4" Rod
6 Sol. (0.162) 2/0 Str. (0.419)
1.97 [50]
0.88 [22]
2.13 [54]
YGHHC29C26
997
U997
U997
U997
2
3/0 Str. (0.470) 250 kcmil (0.575)
2.06 [52]
0.88 [22]
2.13 [54]
YGHHC29C29
997
U997
U997
U997
2
YGHHC34C26
6 Sol. (0.162) 2/0 Str. (0.419)
2.42 [62]
0.88 [22]
2.13 [54] 1011 U1011
S1011 P1011
4
YGHHC34C29
300 kcmil (0.630) 500 kcmil (0.813)
3/0 Str. (0.470) 250 kcmil (0.575)
2.67 [68]
0.88 [22]
2.13 [54] 1011 U1011
S1011 P1011
4
YGHHC34C34
300 kcmil (0.630) 500 kcmil (0.813)
300 kcmil (0.630) 500 kcmil (0.813)
2.91 [74]
1.10 [28]
2.58 [66] 1011 U1011
S1011 P1011
6
45 Series tools require PT6515 adapter to use "U" or "PU" die 46 Series tools require PUADP1 adapter to use "U" or "PU" die
Ground Rod Dia.
PRECRIMP Dies
When attaching connector to ground rod, ground rod must be embossed with appropriate PRECRIMP die. For connectors that must meet IEEE 837 requirements, UPRECRIMP-type precrimp dies must be used for maximum clamping retention. No precrimp needed if using S1012, P1011 or U1011 die sets. These connectors cannot be installed with the 35 Series
UPRECRIMP12 UPRECRIMP58 UPRECRIMP34
1/2" 5/8" 3/4"
U2CABT