Mechanical Grounding
Cable Tray Bonding Straps Cable Tray Bonding Straps
BURNDY Cable Tray Bonding Straps are used to create an electrical bonding connection between two sections of cable tray to ensure a continuous path to ground. NEC Article 250.96 requires all metallic cable trays to be grounding regardless of whether or not the cable tray is being used as an equipment grounding conductor (EGC).
Cable Tray
MinimumSize Equipment GroundingConductors for GroundingRaceway andEquipment ( excerpt of NECTable 250.122) Rating or Setting of Automatic Overcurrent Device inCircuit Ahead Size (AWGor kcmil)
Bonding Braid
Cable Tray
Aluminumor Copper-Clad Aluminum*
of Equipment, Conduit, etc., Not Exceeding (Amperes)
Copper
200 300 400 500 600 800
6 4 3 2 1
4 2 1
1/0 2/0 3/0 4/0 250 350
1/0 2/0 3/0 4/0 250
1000 1200 1600 2000
400 NOTE: Where necessary to comply with 250.4(A)(5) or (B)(4), the equipment grounding conductor shall be sized larger than given in this table. *See installation restrictions in 250.120
BURNDY Cable Tray Bonding Straps
Overcurrent Protection Device Rating (Amperes)
** Length (inches)
** AWG Size or Equivalent
** Stud Size
Catalog Number
Type
BB048L12T38 BB067L12T38
300 500 600 600
#4 #2 #1 #1
12 12 12 12 12 12
3/8” 3/8” 3/8” 3/8”
Braid Braid Braid Braid Braid Braid
BD12T38
CY1CL14D50LT38
14.5
Jumper
BE12T716 BF12T716 BG12T12
1000 1600 2000
2/0 4/0
7/16” 7/16”
250 kcmil
1/2”
**Other lengths, hole sizes, and AWG sizes or equivalents may be available, contact Customer Service Jumpers are manufactured using stranded bare copper code conductor with BURNDY UL Listed compression connectors on each end; Braid is manufactured of tinned, pure copper wire woven and flattened into rectangular shape for greater flexibility; ends of braids feature seamless copper ferrules.