2020 BURNDY Master Catalog
Compression Connections
Copper Compression — Flex — Two Hole Narrow Tongue, Standard Barrel —with Inspection Window
TYPE YAV-L-2NT-FX (Continued)
Straight
45°
90°
NOTE: Field bending straight lugs to achieve an angular connection will void UL Listing / CSA Certifications and BURNDY will not be liable for the connection.
FigureDimen sions
Conductor Stud Hole Size AWG/ KCMIL MM² ***
Installation Tooling
Stud Hole Spacing
Wire Strip Length
Tongue Width
CatalogNumber
MD6, OUR840, MD734R
Dieless (# of crimps) 644 Series (1) 444 Series (1) 81KSeries (1) 644 Series (1) 444 Series (1) 81KSeries (1) 644 Series (1) 444 Series (1) 81KSeries (1) 644 Series (1) 444 Series (1) 81KSeries (1) 644 Series (1) 444 Series (1) 81KSeries (1) 644 Series (1) 444 Series (1) 81KSeries (1) 644 Series (1) 444 Series (1) 81KSeries (1) 644 Series (1) 444 Series (1) 81KSeries (2) 644 Series (1) 444 Series (1) 81KSeries (2)
Color Code
Die Index
(B) (T) (L)
500 Series 35, 750, 46* Series
300 kcmil G,H,I,K,M DLO313 350 kcmil G,H,I,K,M DLO373
W31VT (2) W31RT (2) W32VT (2) W32RT (2)
YA32L2NT38FX
185 3/8 1.00"
0.96 1.19 0.20 3.69
W31VT (2)
U31RT (2)
Red 18 1-1/4
YA34L2NT38FX
240 3/8
1
0.96 1.27 0.23 3.88
W32VT (2)
U32RT (2)
Blue 19 or 470 1-5/16
YA36L2NT38FX
— 3/8 1.00"
1.63 1.38 0.27 4.24
—
— U34RT (2)
500 kcmil G,H DLO444
Brown 20
YA36L2ENT38E10FX
—
— U34RT (2)
— 3/8 1.25 1.50 1.38 0.27 4.49
YA38L2ENT38FX
300 3/8 1.00"
1.50 1.45 0.27 4.35
—
— U38XRT (2)
1-7/16
500 kcmil H,I,K 550 kcmil G,H,I DLO535 650 kcmil G DLO646 750 kcmil G,H DLO777 929 kcmil DLO
YA38L2NT38FX
300 3/8
1
1.63 1.45 0.27 4.35
—
— U38XRT (2)
Pink L99
YA38L2NNTFX
300 1/2 1.75 1.63 1.45 0.27 5.35
—
— U38XRT (2)
YA40L2NNTFX
400 1/2 1.75 1.63 1.42 0.30 5.38
—
— U39RT (2)
Black 24 1-5/16
YA44L2NNTFX YA44L2NT38FX
1/2 1.75 1.63 1.65 0.33 5.74
500
—
— U44XRT (2) •P44XRT (2) Yellow L115 1-5/8
3/8
1
1.63 1.65 0.33 4.74
YA45L2NT38FX
— 3/8 1.00"
1.70 2.00 0.38 5.18
—
— P44RT (2)
White 27 2-1/16
—
Consult cable manufacturers for stress relief instructions ♦ For applications greater than 2000 Volts consult cable manufacturer for voltage stress relief instructions * Use PUADP1 adaptor with U dies in 46 Series • P-RT dies for 46 Series Tooling only *** The MM 2 conductor sizes Listed are the recommendations for Class 5 conductor ▲See tooling section of this catalog for complete tool and die listings. Use ONLY color-coded die recommendations for -FX connectors Note: All dimensions shown are for reference only
1-800-465-7051 (Canada) 1-603-647-5299 (International)
C-73
Made with FlippingBook Ebook Creator